Duct Smoke Detector Sampling Tube Installation

Location And Installation Of Detectors In Air Duct Systems Fire Alarms Certified

Location And Installation Of Detectors In Air Duct Systems Fire Alarms Certified

Midsouthelectronics Com Photoelectric Smoke Duct Detector And Sampling Tube Federal Signal

Midsouthelectronics Com Photoelectric Smoke Duct Detector And Sampling Tube Federal Signal

Source

Source

Duct Smoke Detectors

Duct Smoke Detectors

How To Remove Pipe Inside Duct Detector From System Sensor Youtube

How To Remove Pipe Inside Duct Detector From System Sensor Youtube

Ari Catalog Hvac Installation Accessories Duct Smoke Detectors Sampling Tubes

Ari Catalog Hvac Installation Accessories Duct Smoke Detectors Sampling Tubes

Ari Catalog Hvac Installation Accessories Duct Smoke Detectors Sampling Tubes

The inlet sampling tube is to be located between blades to avoid blockage of the airflow past the tube.

Duct smoke detector sampling tube installation.

A sampling tube must be ordered to complete the installation. Duct detectors smoke detection installation. The sampling tube end cap included with the detector is critical to proper operation of the duct smoke detector. Once any sampling tube length adjustments are made plug the end of the sampling tube with the provided end cap.

Verify this by checking specifications of installation and if necessary use an alnor model 6000p velocity meter or equivalent to check the air. 4 detector installation 4 1 verify duct air flow direction and velocity. It must be the correct length for the width of the duct where it will be installed. Prior to the installation of the damper and smoke detector.

St 10 for duct widths of 6 to 1 0 st 25 for duct widths of 1 0 to 3 0 st 50 for duct widths of 3 0 to 5 0 requires support. The end cap is needed to cre ate the proper air flow to the sensor of the duct smoke detector. One sampling tube end cap 5. Sensor power board assembly and cover s 2.

Verify this by checking specifications of installation and if necessary use an alnor model 6000p velocity meter or equivalent to check the air velocity. Once any sampling tube length adjustments are made plug the end of the sampling tube with the provided end cap. Furthermore intentions for using duct smoke detectors should not be a substitute for area smoke detectors. For proper air sampling duct pressure should be a minimum of 0 01 inches of water.

Three 10 sheet metal screws for mounting 3. One plastic exhaust tube. Sampling tubes install from front or rear of detector compatible with existing accessories 4 contents of the duct smoke detector kit 1. The end cap is needed to create the proper air flow to the sensor of the duct smoke detector.

Duct preparation the duct detectors are designed for use in ducts where the air velocities are from 300 to 4000 feet per minute. Duct smoke detector a. Standard location when factory mounted will be on the side opposite the damper actuator. Installation instructions for the duct smoke detector a.

The sampling tube end cap included with the detector is critical to proper operation of the duct smoke detector. See table 1 on page 3 to determine the inlet tube required for different duct widths. 4 6 p n 3101210 rev 02 iss 28jan13. E pdd duct smoke detector installation sheet operation the duct smoke detector s primary purpose is to provide early.

The specified operating range of the detector make sure the sampling tube air holes are not obstructed and are facing the hvac system airflow. High performance hvac on march 11 2020 at 10 27 pm.

Air Products And Controls Inc Sts25 2 5 Ft Sampling Tube For Sm 501 Series Duct Smoke At Controls Central

Air Products And Controls Inc Sts25 2 5 Ft Sampling Tube For Sm 501 Series Duct Smoke At Controls Central

Duct Smoke Detector Sampling Tube

Duct Smoke Detector Sampling Tube

Installation Instructions For The Duct Smoke Detector Manualzz

Installation Instructions For The Duct Smoke Detector Manualzz

System Sensor Sampling Tube Smoke Detector 2gwl3 Dst3 Grainger

System Sensor Sampling Tube Smoke Detector 2gwl3 Dst3 Grainger

Source : pinterest.com